feat(monitoring): add comprehensive hardware exporter alerts
Added 20 new alerts across 3 rule groups: Power (8 new): - UPSAlarmsActive, UPSBatteryDegraded, UPSOverloaded, UPSOutputVoltageAbnormal - ATSFault, ATSPowerFault, ATSOverload, ATSInputVoltageAbnormal Server Health (10 new): - iDRACSystemUnhealthy, iDRACPowerSupplyUnhealthy, iDRACMemoryUnhealthy - iDRACStorageDriveUnhealthy, iDRACSSDWearCritical/Warning - iDRACServerPoweredOff, ProxmoxExporterDown - FuseMainFault, FuseGarageFault Metric Staleness (3 new): - FuseMainMetricsMissing, FuseGarageMetricsMissing, ProxmoxMetricsMissing Plus 4 new inhibition rules for alert cascade protection.
This commit is contained in:
parent
6abc0b9742
commit
91242b0b40
1 changed files with 164 additions and 1 deletions
|
|
@ -97,7 +97,21 @@ alertmanager:
|
|||
- source_matchers:
|
||||
- alertname = PowerOutage
|
||||
target_matchers:
|
||||
- alertname =~ "NodeDown|NFSServerUnresponsive|NodeExporterDown|CloudflaredDown|MetalLBSpeakerDown|MetalLBControllerDown|UPSMetricsMissing|iDRACRedfishMetricsMissing|iDRACSNMPMetricsMissing|ATSMetricsMissing|HomeAssistantMetricsMissing"
|
||||
- alertname =~ "NodeDown|NFSServerUnresponsive|NodeExporterDown|CloudflaredDown|MetalLBSpeakerDown|MetalLBControllerDown|UPSMetricsMissing|iDRACRedfishMetricsMissing|iDRACSNMPMetricsMissing|ATSMetricsMissing|HomeAssistantMetricsMissing|FuseMainMetricsMissing|FuseGarageMetricsMissing|ProxmoxMetricsMissing|iDRACSystemUnhealthy|iDRACServerPoweredOff|ProxmoxExporterDown"
|
||||
# iDRAC system-level unhealthy suppresses component-level alerts
|
||||
- source_matchers:
|
||||
- alertname = iDRACSystemUnhealthy
|
||||
target_matchers:
|
||||
- alertname =~ "iDRACPowerSupplyUnhealthy|iDRACMemoryUnhealthy|iDRACStorageDriveUnhealthy|FanFailure"
|
||||
# Fuse panel fault suppresses overcurrent/temp alerts for that panel
|
||||
- source_matchers:
|
||||
- alertname = FuseMainFault
|
||||
target_matchers:
|
||||
- alertname = FuseMainMetricsMissing
|
||||
- source_matchers:
|
||||
- alertname = FuseGarageFault
|
||||
target_matchers:
|
||||
- alertname = FuseGarageMetricsMissing
|
||||
# Containerd broken suppresses downstream pod alerts
|
||||
- source_matchers:
|
||||
- alertname = KubeletImagePullErrors
|
||||
|
|
@ -755,6 +769,134 @@ serverFiles:
|
|||
severity: info
|
||||
annotations:
|
||||
summary: "On inverter for >24h - check grid switchover"
|
||||
- alert: UPSAlarmsActive
|
||||
expr: ups_upsAlarmsPresent > 0
|
||||
for: 5m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "UPS has {{ $value }} active alarm(s)"
|
||||
- alert: UPSBatteryDegraded
|
||||
expr: ups_upsBatteryStatus != 2
|
||||
for: 1h
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "UPS battery status abnormal ({{ $value }}, expected 2=normal)"
|
||||
- alert: UPSOverloaded
|
||||
expr: ups_upsOutputPercentLoad{upsOutputLineIndex="1"} > 80
|
||||
for: 15m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "UPS load: {{ $value }}% (threshold: 80%)"
|
||||
- alert: UPSOutputVoltageAbnormal
|
||||
expr: ups_upsOutputVoltage{upsOutputLineIndex="1"} < 210 or ups_upsOutputVoltage{upsOutputLineIndex="1"} > 250
|
||||
for: 5m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "UPS output voltage: {{ $value }}V (expected 210-250V)"
|
||||
- alert: ATSFault
|
||||
expr: automatic_transfer_switch_fault != 0
|
||||
for: 2m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "ATS fault detected (value: {{ $value }})"
|
||||
- alert: ATSPowerFault
|
||||
expr: automatic_transfer_switch_power_fault != 0
|
||||
for: 2m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "ATS power fault detected (value: {{ $value }})"
|
||||
- alert: ATSOverload
|
||||
expr: automatic_transfer_switch_load_power_watts > 3000
|
||||
for: 10m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "ATS load: {{ $value | printf \"%.0f\" }}W (threshold: 3000W)"
|
||||
- alert: ATSInputVoltageAbnormal
|
||||
expr: automatic_transfer_switch_voltage_l1_volts < 200 or automatic_transfer_switch_voltage_l1_volts > 260
|
||||
for: 5m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "ATS input voltage: {{ $value | printf \"%.0f\" }}V (expected 200-260V)"
|
||||
- name: Server Health
|
||||
rules:
|
||||
- alert: iDRACSystemUnhealthy
|
||||
expr: r730_idrac_redfish_system_health_state != 1
|
||||
for: 5m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "iDRAC system health state: {{ $value }} (expected 1=OK)"
|
||||
- alert: iDRACPowerSupplyUnhealthy
|
||||
expr: r730_idrac_redfish_chassis_power_powersupply_health != 1
|
||||
for: 5m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "iDRAC PSU {{ $labels.member_id }} unhealthy (state: {{ $value }})"
|
||||
- alert: iDRACMemoryUnhealthy
|
||||
expr: r730_idrac_redfish_system_memory_health_state != 1
|
||||
for: 5m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "iDRAC memory subsystem unhealthy (state: {{ $value }})"
|
||||
- alert: iDRACStorageDriveUnhealthy
|
||||
expr: r730_idrac_redfish_system_storage_drive_health_state != 1
|
||||
for: 5m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "iDRAC storage drive {{ $labels.member_id }} unhealthy (state: {{ $value }})"
|
||||
- alert: iDRACSSDWearCritical
|
||||
expr: r730_idrac_idrac_storage_drive_life_left_percent > 0 and r730_idrac_idrac_storage_drive_life_left_percent < 10
|
||||
for: 1h
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "SSD {{ $labels.id }} has {{ $value }}% life remaining"
|
||||
- alert: iDRACSSDWearWarning
|
||||
expr: r730_idrac_idrac_storage_drive_life_left_percent > 0 and r730_idrac_idrac_storage_drive_life_left_percent < 20
|
||||
for: 6h
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "SSD {{ $labels.id }} has {{ $value }}% life remaining"
|
||||
- alert: iDRACServerPoweredOff
|
||||
expr: r730_idrac_redfish_system_power_state != 2
|
||||
for: 3m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "R730 server is not powered on (state: {{ $value }}, expected 2=On)"
|
||||
- alert: ProxmoxExporterDown
|
||||
expr: pve_up{id="node/pve"} == 0
|
||||
for: 5m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "Proxmox exporter cannot reach PVE host"
|
||||
- alert: FuseMainFault
|
||||
expr: fuse_main_fault != 0
|
||||
for: 2m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "Main fuse panel fault detected"
|
||||
- alert: FuseGarageFault
|
||||
expr: fuse_garage_fault != 0
|
||||
for: 2m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "Garage fuse panel fault detected"
|
||||
- name: Metric Staleness
|
||||
rules:
|
||||
- alert: UPSMetricsMissing
|
||||
|
|
@ -785,6 +927,27 @@ serverFiles:
|
|||
severity: warning
|
||||
annotations:
|
||||
summary: "ATS metrics missing for 15m - check tuya-bridge pod"
|
||||
- alert: FuseMainMetricsMissing
|
||||
expr: absent(fuse_main_voltage)
|
||||
for: 15m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "Fuse main panel metrics missing for 15m - check tuya-bridge pod"
|
||||
- alert: FuseGarageMetricsMissing
|
||||
expr: absent(fuse_garage_voltage)
|
||||
for: 15m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "Fuse garage panel metrics missing for 15m - check tuya-bridge pod"
|
||||
- alert: ProxmoxMetricsMissing
|
||||
expr: absent(pve_up)
|
||||
for: 10m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "Proxmox metrics missing for 10m - check proxmox-exporter pod"
|
||||
- alert: HomeAssistantMetricsMissing
|
||||
expr: absent(up{job="haos"})
|
||||
for: 10m
|
||||
|
|
|
|||
Loading…