@ -168,15 +168,89 @@ serverFiles:
|
|||
# targets: "alertmanager.viktorbarzin.lan"
|
||||
alerting_rules.yml:
|
||||
groups:
|
||||
- name: Cluster
|
||||
- name: R730 Host
|
||||
rules:
|
||||
- alert: LowVoltage
|
||||
expr: ups_upsInputVoltage < 205
|
||||
- alert: HighCPUTemperature
|
||||
expr: node_hwmon_temp_celsius{instance="pve-node-r730"} * on(chip) group_left(chip_name) node_hwmon_chip_names{instance="pve-node-r730"} > 75
|
||||
for: 30m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "High CPU Temperature: {{ $value }}."
|
||||
- alert: SSDHighWriteRate
|
||||
expr: rate(node_disk_written_bytes_total{job="proxmox-host", device="sdb"}[2m]) / 1024 / 1024 > 2 # sdb is SSD; value in MB
|
||||
for: 10m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "Low input voltage - {{ $value }}"
|
||||
summary: "High write rate on SSD - {{ $value }}MB"
|
||||
- alert: HDDHighWriteRate
|
||||
expr: rate(node_disk_written_bytes_total{job="proxmox-host", device="sdc"}[2m]) / 1024 / 1024 > 10 # sdc is 11TB HDD; value in MB
|
||||
for: 20m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "High write rate on HDD - {{ $value }}MB"
|
||||
- alert: NoiDRACData
|
||||
expr: (max(r730_idrac_idrac_system_health + 1) or on() vector(0)) == 0
|
||||
for: 30m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: No iDRAC amperage reading. Can signal that prometheus is not scraping
|
||||
- alert: HighRAMUsage
|
||||
expr: clamp_min((1 - (node_memory_MemAvailable_bytes{instance="pve-node-r730"} / node_memory_MemTotal_bytes{instance="pve-node-r730"})) * 100, 0) > 90
|
||||
for: 30m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "High memory usage: {{ $value }}. Risk of OOM-ing."
|
||||
- alert: HighSystemLoad
|
||||
expr: scalar(node_load1{instance="pve-node-r730"}) * 100 / count(count(node_cpu_seconds_total{instance="pve-node-r730"}) by (cpu)) > 50
|
||||
for: 30m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "High system load: {{ $value }}. Can signal runaway process."
|
||||
- alert: DockerRegistryDown
|
||||
expr: (registry_process_start_time_seconds or on() vector(0)) == 0
|
||||
for: 10m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "Docker registry is down"
|
||||
- name: Nvidia Tesla T4 GPU
|
||||
rules:
|
||||
- alert: HighGPUTemp
|
||||
expr: nvidia_tesla_t4_DCGM_FI_DEV_GPU_TEMP > 65
|
||||
for: 1m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "High GPU Temperature {{$value}}"
|
||||
- alert: HighPowerUsage
|
||||
expr: nvidia_tesla_t4_DCGM_FI_DEV_POWER_USAGE > 50
|
||||
for: 30m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "High GPU power usage {{$value}}"
|
||||
- alert: HighUtilization
|
||||
expr: nvidia_tesla_t4_DCGM_FI_DEV_GPU_UTIL > 50
|
||||
for: 30m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "High GPU utilization {{$value}}"
|
||||
- alert: HighMemoryUsage
|
||||
expr: nvidia_tesla_t4_DCGM_FI_DEV_FB_USED / 1024 > 12
|
||||
for: 5m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "High VRAM usage {{$value}}"
|
||||
- name: Power
|
||||
rules:
|
||||
- alert: OnBattery
|
||||
expr: ups_upsSecondsOnBattery > 0
|
||||
for: 30m
|
||||
|
|
@ -184,13 +258,35 @@ serverFiles:
|
|||
severity: critical
|
||||
annotations:
|
||||
summary: "UPS on battery for {{ $value }} seconds"
|
||||
- alert: LowUPBattery
|
||||
- alert: LowUPSBattery
|
||||
expr: ups_upsEstimatedMinutesRemaining < 25 and on(instance) ups_upsInputVoltage < 150
|
||||
for: 1m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "UPS battery running out - {{ $value }} minutes remaining"
|
||||
- alert: PowerOutage
|
||||
expr: ups_upsInputVoltage < 150
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: Power voltage on a power supply is {{ $value }} indicating power outage.
|
||||
- alert: HighPowerUsage
|
||||
expr: r730_idrac_idrac_power_control_consumed_watts > 200
|
||||
for: 60m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "High server power usage - {{$value}} watts"
|
||||
- alert: UsingInverterEnergyForTooLong
|
||||
expr: automatic_transfer_switch_power_mode > 0 # 1 = Inverter; 0 = Grid
|
||||
for: 24h
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "Running on inverter for too long: {{ $value }}%. Maybe switching to grid does not work."
|
||||
- name: Cluster
|
||||
rules:
|
||||
- alert: NodeDown
|
||||
expr: (up{job="kubernetes-nodes"} or on() vector(0)) == 0
|
||||
for: 1m
|
||||
|
|
@ -212,13 +308,6 @@ serverFiles:
|
|||
severity: page
|
||||
annotations:
|
||||
summary: "Low free memory on {{ $labels.node }} - {{ $value }}"
|
||||
- alert: SSDHighWriteRate
|
||||
expr: rate(node_disk_written_bytes_total{job="proxmox-host", device="sdb"}[2m]) / 1024 / 1024 > 2 # sdb is SSD; value in MB
|
||||
for: 10m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "High write rate on SSD - {{ $value }}MB"
|
||||
# - name: PodStuckNotReady
|
||||
# rules:
|
||||
# - alert: PodStuckNotReady
|
||||
|
|
@ -235,26 +324,6 @@ serverFiles:
|
|||
# severity: page
|
||||
# annotations:
|
||||
# summary: Number of ready pods in {{ $labels.deployment }} is less than what is defined in spec.
|
||||
- alert: PowerOutage
|
||||
expr: ups_upsInputVoltage < 150
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: Power voltage on a power supply is {{ $value }} indicating power outage.
|
||||
- alert: HighGPUTemp
|
||||
expr: nvidia_tesla_t4_DCGM_FI_DEV_GPU_TEMP > 65
|
||||
for: 1m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "High GPU Temperature {{$value}}"
|
||||
- alert: HighPowerUsage
|
||||
expr: r730_idrac_idrac_power_control_consumed_watts > 200
|
||||
for: 60m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "High server power usage - {{$value}} watts"
|
||||
- alert: NoNodeLoadData
|
||||
expr: (node_load1 OR on() vector(0)) == 0
|
||||
for: 10m
|
||||
|
|
@ -262,13 +331,6 @@ serverFiles:
|
|||
severity: page
|
||||
annotations:
|
||||
summary: No node load data. Can signal that prometheus is not scraping
|
||||
- alert: NoiDRACData
|
||||
expr: (max(r730_idrac_idrac_system_health + 1) or on() vector(0)) == 0
|
||||
for: 30m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: No iDRAC amperage reading. Can signal that prometheus is not scraping
|
||||
- alert: HighIngressPermissionErrors
|
||||
expr: (sum(rate(nginx_ingress_controller_requests{status=~"4.*", ingress!="nextcloud", ingress!="grafana"}[2m])) by (ingress) / sum(rate(nginx_ingress_controller_requests[2m])) by (ingress) * 100) > 10
|
||||
for: 20m
|
||||
|
|
@ -283,20 +345,6 @@ serverFiles:
|
|||
severity: page
|
||||
annotations:
|
||||
summary: "High server failiure rate for {{ $labels.ingress }}: {{ $value }}%."
|
||||
- alert: UsingInverterEnergyForTooLong
|
||||
expr: automatic_transfer_switch_power_mode > 0 # 1 = Inverter; 0 = Grid
|
||||
for: 24h
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "Running on inverter for too long: {{ $value }}%. Maybe switching to grid does not work."
|
||||
- alert: DockerRegistryDown
|
||||
expr: (registry_process_start_time_seconds or on() vector(0)) == 0
|
||||
for: 10m
|
||||
labels:
|
||||
severity: page
|
||||
annotations:
|
||||
summary: "Docker registry is down"
|
||||
# - alert: OpenWRT High Memory Usage
|
||||