# PVE R730 presence-aware fan control — design **Date:** 2026-06-04 **Status:** implemented **Scripts:** `infra/scripts/fan-control.{sh,service,env.example}`, `test-fan-control.sh` **Runbook:** `infra/docs/runbooks/fan-control.md` ## Problem The Dell R730 PVE host (192.168.1.127) runs its CPU at ~72–77°C under normal cluster load. That is safe (firmware warning at 88°C, critical 93°C) but the iDRAC's stock fan curve optimises for quiet, not cool — it pins the fans at the ~7080 RPM floor even at 72°C / load 30 and only ramps near ~80°C. We want the CPU to run cooler when it costs nothing (the box is in the garage, usually empty) while staying quiet when someone is physically in the garage. ## Measured fan/temp relationship (manual IPMI sweep, 2026-06-04) At a comparable CPU load (~45–53 % busy): | Fan setting | Fan RPM | CPU temp | |-------------|---------|----------| | Auto (floor) | 7,080 | 71–72°C | | 50 % | 9,360 | 65–66°C | | 70 % | 12,800 | 60–61°C | | 100 % | 17,000 | 55–56°C | Best °C-per-RPM is the first step; beyond ~70 % it is mostly noise. ~16°C of swing is available. ## Power characterization (sweep 2026-06-05) Averaged wall power (iDRAC DCMI) + temp at each fan setting: | Fan | RPM | Power | CPU | load | |-----|-----|-------|-----|------| | auto | 7,080 | 296 W | 68°C | 21 | | 20 % | 4,800 | 281 W | 73°C | 20 | | 30 % | 6,360 | 288 W | 72°C | 19 | | 50 % | 9,360 | 299 W | 65°C | 18 | | 60 % | 11,040 | 303 W | 61°C | 17 | | 70 % | 12,720 | 324 W | 59°C | 16 | | 100 % | 16,920 | 378 W | 59°C | 17 | **The cooling-per-watt knee is ~60 %.** Fan power follows ~RPM³: 60→70 % costs +21 W for −2°C; 70→100 % costs **+54 W for 0°C** (the CPU floors ~59°C at cluster load — more airflow does nothing). Full speed draws ~97 W (~850 kWh/yr) over the floor and buys nothing past 60 %. **Decision (2026-06-05):** the COOL curve caps its normal band at 60 % (~303 W, ~61°C) — capturing essentially all achievable cooling while avoiding the wasteful 80–100 % zone, now reserved as a high-load safety ramp (≥73/79°C) before the 83°C ceiling. QUIET is unchanged (already at the low-power floor: 20 % / 4,800 RPM / 281 W). Verified live after re-tune: 63°C, 60 %, ~267 W. ## Decisions 1. **Custom bash daemon + systemd service**, deployed to the PVE host the same way as `apply-mbps-caps` / `daily-backup` (source in `infra/scripts/`, scp to `/usr/local/bin`). It cannot be Terraform/k8s — it runs on the bare host where IPMI lives. (OSS `tigerblue77/Dell-iDRAC-fan-controller` was considered; rejected — it is a Docker container, off-pattern here, and unaware of our constraints.) 2. **CPU temperature is the only control input.** The Tesla T4 has its own always-on fan (owner-confirmed), so it self-cools and does not depend on chassis airflow — no GPU coupling needed. 3. **Presence = the garage door**, because the server is *in the garage* (memory id=1723); noise only matters to people physically there. Signal: ha-sofia `sensor.garage_door_state_bg`. Open now, or last changed within `HOLD_SECS` (15 min) ⇒ someone's around ⇒ QUIET; otherwise COOL. `house_mode` was rejected — it tracks *apartment* occupancy, irrelevant to garage noise. 4. **Two continuous LINEAR curves**, picked by presence. (Originally discrete step-bands; replaced 2026-06-05 — the bands flapped at edges, e.g. 45↔65%. Web research: a linear curve + 2–3°C hysteresis is the homelab standard; PID is overkill for this slow thermal loop and even PID projects "only lower, don't chase a setpoint".) fan% interpolates between per-mode anchors, clamped flat outside; both reach 100% right at the 83°C ceiling: | Mode | T_LO → P_LO | T_HI → P_HI | slope | |------|-------------|-------------|-------| | COOL (garage empty) | 50°C → 30% | 83°C → 100% | ~2.1%/°C (≈51% at the ~60°C equilibrium) | | QUIET (occupied) | 68°C → 20% | 83°C → 100% | ~4.7%/°C (near-silent until ~70°C) | Anchors are env-tunable (`COOL_T_LO/P_LO/T_HI/P_HI`, `QUIET_*`). Under normal load the COOL equilibrium (~60°C → ~51%) sits near the measured ~60% power knee; the ramp toward 100% only engages at genuinely high temp (safety). Anti-oscillation: asymmetric hysteresis (ramp up immediately, ease down only once the curve wants lower 3°C hotter) **plus** a `MIN_STEP` (3%) min-change threshold so 1–2% wiggles don't churn IPMI writes. ## Safety Manual fan mode bypasses the iDRAC's own protection, so it is backstopped: - **Daemon exit/crash/stop** → bash `EXIT` trap + systemd `ExecStopPost` both run `ipmitool raw 0x30 0x30 0x01 0x01` (restore Dell auto). `Restart=on-failure`. - **CPU ≥ `CEILING` (83°C)** → hand back to Dell auto until temp holds below `RESUME_BELOW` (75°C) for `RESUME_STABLE` (120 s), then resume manual. - **IPMI read failures ≥ `MAX_IPMI_FAILS`** → restore Dell auto. - **ha-sofia unreachable** → keep the last good presence decision; default COOL at cold start (thermally safe). ## Observability Pushes to the Pushgateway (`http://10.0.20.100:30091`, job `fan_control`): `pve_fan_control_cpu_temp_celsius`, `_fan_percent`, `_mode` (1 quiet / 2 cool / 3 manual / 0 fallback), `_ha_reachable`, `_fallback`, `_fan_rpm`, and `_fan_watts_est`. **Fan power is ESTIMATED** — the iDRAC exposes only total DCMI watts + RPM (no per-fan power), so `_fan_watts_est` models it from RPM via the fan affinity law (power ∝ RPM³), calibrated to the 2026-06-05 sweep: `fan_W ≈ 0.0205·(RPM/1000)³` (≈2 W at the floor → ~99 W at full; fits the sweep within ~3 W). Surfaced in HA as `sensor.r730_fan_power_est` + a "Fan Power (est)" card on the dashboard-it Server view, next to total power (`sensor.r730_power_consumption`, redfish) — so the fan tax of the control curve is visible. The existing CPU-temp alert is unaffected. ## Testing `test-fan-control.sh` sources the script (main is guarded by a `BASH_SOURCE` check) and unit-tests the pure functions: both curves, hysteresis up/down, presence open/recent/stale, temperature parsing, jq-free JSON field extraction, and percent→hex. 36 assertions, no hardware needed. The daemon also supports `DRY_RUN=1` and `RUN_ONCE=1` for integration checks. ## HA control (added 2026-06-05, on the host daemon) Delivered ahead of the cron migration (which is Vault-gated) by teaching the **host daemon** to poll two ha-sofia helpers each loop (`fc_resolve`): `input_select.r730_fan_mode` (auto/cool/quiet/manual) + `input_number.r730_fan_manual_pct`. `auto` = the garage-presence curve above; cool/quiet force that curve; manual holds a fixed %; `CEILING` still overrides. The **simplified dashboard (2026-06-05)** exposes just three things — fan speed (%/RPM), an **Override %** slider, and a **Lock** toggle. Lock = "freeze current speed / algo off": `automation.r730_fan_lock_freeze_current_speed_resume_algo` snapshots the live target % into Override and sets `mode=manual` on lock-ON, and `mode=auto` on lock-OFF — the daemon needs no change, the toggle just drives the mode. `cool`/`quiet` stay reachable via the entity but are off the dashboard. The 60-min `automation.r730_fan_mode_auto_revert` is retained as a dormant safety net (manual now only happens while locked, which it skips). The daemon just polls and actuates. Monitoring + control live on the dashboard-it "Server" view (REST sensors: fan RPM from the redfish exporter; mode/target-% from the Pushgateway). The same logic already exists in the Python controller (`r730-fan-control/`) for the eventual in-cluster CronJob; when that deploys it supersedes the host daemon. ## Rollback `systemctl disable --now fan-control && ipmitool raw 0x30 0x30 0x01 0x01` on the host returns the box to stock firmware fan control. See the runbook.