Power/temp sweep (2026-06-05) located the cooling-per-watt knee at ~60%: 60->70% buys only -2C for +21W, and 70->100% buys 0C for +54W (the CPU floors ~59C at cluster load, so more airflow does nothing). Re-tune the COOL curve to cap its normal band at 60% (~303W, ~61C); 80/100% become a high-load safety ramp (>=73/79C) before the 83C ceiling. QUIET unchanged (already at the 281W / 4800rpm floor). Saves up to ~75W (~650 kWh/yr) vs full-tilt for the last ~2C. Tests + design doc updated; verified live (63C, 60%, ~267W). [ci skip] Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
117 lines
5.2 KiB
Markdown
117 lines
5.2 KiB
Markdown
# PVE R730 presence-aware fan control — design
|
||
|
||
**Date:** 2026-06-04
|
||
**Status:** implemented
|
||
**Scripts:** `infra/scripts/fan-control.{sh,service,env.example}`, `test-fan-control.sh`
|
||
**Runbook:** `infra/docs/runbooks/fan-control.md`
|
||
|
||
## Problem
|
||
|
||
The Dell R730 PVE host (192.168.1.127) runs its CPU at ~72–77°C under normal
|
||
cluster load. That is safe (firmware warning at 88°C, critical 93°C) but the
|
||
iDRAC's stock fan curve optimises for quiet, not cool — it pins the fans at the
|
||
~7080 RPM floor even at 72°C / load 30 and only ramps near ~80°C. We want the
|
||
CPU to run cooler when it costs nothing (the box is in the garage, usually
|
||
empty) while staying quiet when someone is physically in the garage.
|
||
|
||
## Measured fan/temp relationship (manual IPMI sweep, 2026-06-04)
|
||
|
||
At a comparable CPU load (~45–53 % busy):
|
||
|
||
| Fan setting | Fan RPM | CPU temp |
|
||
|-------------|---------|----------|
|
||
| Auto (floor) | 7,080 | 71–72°C |
|
||
| 50 % | 9,360 | 65–66°C |
|
||
| 70 % | 12,800 | 60–61°C |
|
||
| 100 % | 17,000 | 55–56°C |
|
||
|
||
Best °C-per-RPM is the first step; beyond ~70 % it is mostly noise. ~16°C of
|
||
swing is available.
|
||
|
||
## Power characterization (sweep 2026-06-05)
|
||
|
||
Averaged wall power (iDRAC DCMI) + temp at each fan setting:
|
||
|
||
| Fan | RPM | Power | CPU | load |
|
||
|-----|-----|-------|-----|------|
|
||
| auto | 7,080 | 296 W | 68°C | 21 |
|
||
| 20 % | 4,800 | 281 W | 73°C | 20 |
|
||
| 30 % | 6,360 | 288 W | 72°C | 19 |
|
||
| 50 % | 9,360 | 299 W | 65°C | 18 |
|
||
| 60 % | 11,040 | 303 W | 61°C | 17 |
|
||
| 70 % | 12,720 | 324 W | 59°C | 16 |
|
||
| 100 % | 16,920 | 378 W | 59°C | 17 |
|
||
|
||
**The cooling-per-watt knee is ~60 %.** Fan power follows ~RPM³: 60→70 % costs
|
||
+21 W for −2°C; 70→100 % costs **+54 W for 0°C** (the CPU floors ~59°C at cluster
|
||
load — more airflow does nothing). Full speed draws ~97 W (~850 kWh/yr) over the
|
||
floor and buys nothing past 60 %.
|
||
|
||
**Decision (2026-06-05):** the COOL curve caps its normal band at 60 % (~303 W,
|
||
~61°C) — capturing essentially all achievable cooling while avoiding the wasteful
|
||
80–100 % zone, now reserved as a high-load safety ramp (≥73/79°C) before the 83°C
|
||
ceiling. QUIET is unchanged (already at the low-power floor: 20 % / 4,800 RPM /
|
||
281 W). Verified live after re-tune: 63°C, 60 %, ~267 W.
|
||
|
||
## Decisions
|
||
|
||
1. **Custom bash daemon + systemd service**, deployed to the PVE host the same
|
||
way as `apply-mbps-caps` / `daily-backup` (source in `infra/scripts/`, scp to
|
||
`/usr/local/bin`). It cannot be Terraform/k8s — it runs on the bare host where
|
||
IPMI lives. (OSS `tigerblue77/Dell-iDRAC-fan-controller` was considered;
|
||
rejected — it is a Docker container, off-pattern here, and unaware of our
|
||
constraints.)
|
||
2. **CPU temperature is the only control input.** The Tesla T4 has its own
|
||
always-on fan (owner-confirmed), so it self-cools and does not depend on
|
||
chassis airflow — no GPU coupling needed.
|
||
3. **Presence = the garage door**, because the server is *in the garage*
|
||
(memory id=1723); noise only matters to people physically there. Signal:
|
||
ha-sofia `sensor.garage_door_state_bg`. Open now, or last changed within
|
||
`HOLD_SECS` (15 min) ⇒ someone's around ⇒ QUIET; otherwise COOL.
|
||
`house_mode` was rejected — it tracks *apartment* occupancy, irrelevant to
|
||
garage noise.
|
||
4. **Two curves**, picked by presence (COOL power-tuned 2026-06-05 — see
|
||
"Power characterization" below):
|
||
|
||
| CPU °C | COOL % (empty) | CPU °C | QUIET % (occupied) |
|
||
|--------|----------------|--------|--------------------|
|
||
| ≤54 | 30 | ≤72 | 20 (≈silent floor) |
|
||
| 55–63 | 50 | 73–77 | 40 |
|
||
| 64–72 | 60 (knee) | 78–81 | 65 |
|
||
| 73–78 | 80 | ≥82 | 100 |
|
||
| ≥79 | 100 | | |
|
||
|
||
3°C downward hysteresis prevents flapping at band edges (ramp up immediately,
|
||
step down only once the curve still wants lower 3°C hotter).
|
||
|
||
## Safety
|
||
|
||
Manual fan mode bypasses the iDRAC's own protection, so it is backstopped:
|
||
|
||
- **Daemon exit/crash/stop** → bash `EXIT` trap + systemd `ExecStopPost` both
|
||
run `ipmitool raw 0x30 0x30 0x01 0x01` (restore Dell auto). `Restart=on-failure`.
|
||
- **CPU ≥ `CEILING` (83°C)** → hand back to Dell auto until temp holds below
|
||
`RESUME_BELOW` (75°C) for `RESUME_STABLE` (120 s), then resume manual.
|
||
- **IPMI read failures ≥ `MAX_IPMI_FAILS`** → restore Dell auto.
|
||
- **ha-sofia unreachable** → keep the last good presence decision; default COOL
|
||
at cold start (thermally safe).
|
||
|
||
## Observability
|
||
|
||
Pushes to the existing Pushgateway (`http://10.0.20.100:30091`, job
|
||
`fan_control`): `pve_fan_control_cpu_temp_celsius`, `_fan_percent`, `_mode`
|
||
(1 quiet / 2 cool / 0 fallback), `_ha_reachable`, `_fallback`. The existing CPU-
|
||
temp alert is unaffected.
|
||
|
||
## Testing
|
||
|
||
`test-fan-control.sh` sources the script (main is guarded by a `BASH_SOURCE`
|
||
check) and unit-tests the pure functions: both curves, hysteresis up/down,
|
||
presence open/recent/stale, temperature parsing, jq-free JSON field extraction,
|
||
and percent→hex. 36 assertions, no hardware needed. The daemon also supports
|
||
`DRY_RUN=1` and `RUN_ONCE=1` for integration checks.
|
||
|
||
## Rollback
|
||
|
||
`systemctl disable --now fan-control && ipmitool raw 0x30 0x30 0x01 0x01` on the
|
||
host returns the box to stock firmware fan control. See the runbook.
|